Velocity Edge GX440 Instruções de Operação Página 278

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 530
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 277
Setpoint channel and closed-loop control
7.4 Vector speed/torque control with/without encoder
Drive converter cabinet units
278 Operating Instructions, 10/2008, A5E00288214A
p1960
Speed controller optimization selection
7.4.3.1 Examples of speed controller settings
Examples of speed controller settings for vector control with encoders
A number of examples of speed controller settings with vector control without encoders
(p1300 = 20) are provided below. These should not be considered to be generally valid and
must be checked in terms of the control response required.
Fans (large centrifugal masses) and pumps
Kp (p1470) = 2 … 10
Tn (p1472) = 250 … 500 ms
The Kp = 2 and Tn = 500 ms settings result in asymptotic approximation of the actual
speed to the setpoint speed after a setpoint step change. During many simple control
procedures, this is satisfactory for pumps and fans.
Stone mills, separators (large centrifugal masses)
Kp (p1470) = 12 … 20
Tn (p1472) = 500 … 1000 ms
Kneader drives
Kp (p1470) = 10
Tn (p1472) = 200 … 400 ms
Note
We recommend checking the effective speed control gain (r1468) during operation. If this
value changes during operation, Kp adaptation is being used (p1400.5 = 1). Kp
adaptation can, if necessary, be deactivated or its behavior changed.
Vista de página 277
1 2 ... 273 274 275 276 277 278 279 280 281 282 283 ... 529 530

Comentários a estes Manuais

Sem comentários