TTR31, TTR35 Operation
Endress+Hauser 17
5.1.6 Settings for output - 1x switch output and 1x analog output (4 to 20 mA)

Output 1
.
Output 2,
as option

.
Switch-back point
value
,M, Switch-back point
-50 to 149 °C
(-58 to 300 °F)
in increments of 0.1 °C
(0.18 °F)

.
Switch point delay ,M, Delay time
0...99 s
in increments of 0.1 s
Factory setting: 0 s

.
Switch-back point
delay
,M, Delay time 0...99 s
in increments of 0.1 s
Factory setting: 0 s
Min. distance between SP and RSP: 0.5 °C/K (0.9 °F)
Function
group
Function Settings Description

Output 1
.
Output 2,
as option
6
6.
Switching
characteristic




0>.,
WINC:
window/NC contact
HYNC:
hysteresis/NC contact
WINO:
window/NO contact
HYNO:
hysteresis/NO contact
4 - 20: analog output
Factory setting: HYNO

.
Switch point value ,M, Switch point
-49.5 to 150 °C
(-57.1 to 302 °F)
in increments of 0.1 °C
(0.18 °F)
Function
group
Function Settings Description