Velocity Edge GX440 Instruções de Operação Página 205

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 530
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 204
Operation
6.5 Setpoint sources
Drive converter cabinet units
Operating Instructions, 10/2008, A5E00288214A
205
6.5 Setpoint sources
6.5.1 Analog inputs
Description
The customer terminal block TM31 features two analog inputs for specifying setpoints for
current or voltage signals.
In the factory setting, analog input 0 (terminal X521:1/2) is used as a current input in the
range 0 to 20 mA.
Requirement
The default setting for analog inputs was chosen during commissioning:
STARTER:
"TM31 Terminals"
AOP30:
"2: TM31 terminals
6FDOLQJ
&KDU[ &KDU[
&KDU\
&KDU\
6PRRWKLQJ
7\SH
:LUHEUHDNDJHDQDORJLQSXW
&XUU8, &XUUHQWYDOXH
2IIVHW
RQO\ZKHQS 
S S
S
[
\
[

\

[

\

\
[
>@
S
S
$
'
S
6


$,
;
)
U
;
6
6
9
,
,
9
U
S
Figure 6-17 Signal flow diagram: analog input 0
Function diagram
FP 9566 TM31 – analog input 0 (AI 0)
FP 9568 TM31 – analog input 1 (AI 1)
Parameter
r4052
Actual input voltage/current
p4053
Analog inputs smoothing time constant
r4055
Analog inputs, actual input value in percent
p4056
Analog inputs type
p4057
Analog inputs, characteristic value x1
Vista de página 204
1 2 ... 200 201 202 203 204 205 206 207 208 209 210 ... 529 530

Comentários a estes Manuais

Sem comentários