Velocity Edge GX440 Instruções de Operação Página 521

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 530
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 520
Appendix
A.2 Parameter macros
Drive converter cabinet units
Operating Instructions, 10/2008, A5E00288214A
521
Parameter macro p1000 = 1: PROFIdrive (100001)
This macro is used to set the default setpoint source via PROFIdrive.
Table A- 6 Parameter macro p1000 = 1: PROFIdrive
Sink Source
Parameters Description DO Parameters Description DO
p1070 Main setpoint Vector r2050[1] PROFIdrive PZD2 Vector
p1071 Main setpoint scaling Vector 1 100 % Vector
p1075 Supplementary setpoint Vector 0 Vector
p1076 Supplementary setpoint scaling Vector 1 100 % Vector
Parameter macro p1000 = 2: Terminal TM31 (100002)
This macro is used to set analog input 0 on customer terminal block TM31 as the setpoint
source.
Table A- 7 Parameter macro p1000 = 2: TM31 terminals
Sink Source
Parameter Description DO Parameter Description DO
p1070 Main setpoint Vector r4055 AI0 TM31 TM31
p1071 Main setpoint scaling Vector 1 100 % Vector
p1075 Supplementary setpoint Vector 0 Vector
p1076 Supplementary setpoint scaling Vector 1 100 % Vector
Parameter macro p1000 = 3: Motorized potentiometer (100003)
This macro is used to set the motorized potentiometer as the setpoint source.
Table A- 8 Parameter macro p1000 = 3: Motorized potentiometer
Sink Source
Parameters Description DO Parameters Description DO
p1070 Main setpoint Vector r1050 Motorized potentiometer Vector
p1071 Main setpoint scaling Vector 1 100 % Vector
p1075 Supplementary setpoint Vector 0 Vector
p1076 Supplementary setpoint scaling Vector 1 100 % Vector
Vista de página 520
1 2 ... 516 517 518 519 520 521 522 523 524 525 526 ... 529 530

Comentários a estes Manuais

Sem comentários